Openable rectangular frame
Flangeless frame installed by welding.
View references →Designed for installations with existing cables or pipes. Their openable side allows installation around existing services following the official mounting procedure.

Flangeless frame installed by welding.
View references →
10 mm solid flange; welding or casting in the wall.
View references →
6 mm light flange; welding or casting in the wall.
View references →
10 mm holed flange; bolting or casting in the wall.
View references →
6 mm light holed flange; bolting or casting in the wall.
View references →Engineering dimensions and 1 × 1 part references for existing cable and pipe penetrations. Select a series below to inspect its dimensioned drawing and sizing formulas.
Weldable metal frame designed to wrap around pre-installed cables or pipes. Features an openable side for mounting without disconnecting existing cables or pipes.
| Useful packing space | H1 = H - 20 mm · W1 = W - 20 mm |
|---|---|
| Frame depth (D) | 60 mm (2.362 in) |
| Wall thickness (T) / Corner radius | T = 10 mm · Corner radius R10 |
| Mounting | Welding |
Rectangular frames equipped with a continuous 60 mm perimeter flange. WRFFO utilizes a 10 mm thick flange while WRFFLO features a lighter 6 mm flange to reduce structural weight.
| Useful packing space | H1 = H - 120 mm · W1 = W - 120 mm |
|---|---|
| Flange width (f) | f = 60 mm around full perimeter |
| Flange thickness (t1) | WRFFO: 10 mm · WRFFLO: 6 mm |
| Mounting | Cast in wall or welding |
Recommended where welding is impractical or not permitted on site. Its holed perimeter flange allows direct installation by bolting.
| Useful packing space | H1 = H - 120 mm · W1 = W - 120 mm |
|---|---|
| Flange bolt holes | Hole diameter øh = 9 mm · Edge distance dh = 35 mm |
| Flange thickness (t1) | WRHFFO: 10 mm · WRHFFLO: 6 mm |
| Mounting | Bolting or cast in wall |
| Series | Article Code | Configuration | Packing Space (mm) | External Dimensions (mm) | Material | Mounting |
|---|
WallMax® openable frames are used with Regular Modules and matching compression and sealing accessories per series and configuration. WMR is the primary module family; WMRwop, WMS, WE, and WRP are selected as required by the documented system.